OPEN ACCESS

Articles online

Performance of Electret Filters for Use in a Heating, Ventilation and Air Conditioning System and an Automotive Cabin against Combustion and NaCl Particles

Category: Control Techniques and Strategy

Volume: 16 | Issue: 6 | Pages: 1523-1531
DOI: 10.4209/aaqr.2015.09.0565
PDF | RIS | BibTeX

Jin-Yong Kim1, Shuang Gao1, Michael Yermakov1, Yousef Elmashae1, Xinjian He2, Tiina Reponen1, Sergey A. Grinshpun 1

  • 1 Center for Health-Related Aerosol Studies, Department of Environmental Health, University of Cincinnati, Cincinnati, Ohio, USA
  • 2 Department of Industrial and Management Systems Engineering, Statler College of Engineering and Mineral Resources, WV University, Morgantown, West Virginia, USA

Highlights

An HVAC filter and an ACA filter were challenged with combustion and NaCl particles.
Collection efficiency of each filter challenged with two aerosols was determined.
Filtration of NaCl particles is more efficient than that of combustion particles.


Abstract

This study was conducted to investigate the performance of a high-efficiency Heating, Ventilation and Air Conditioning (HVAC) filter and a top-of-the line Automotive Cabin Air (ACA) filter challenged with particles generated by the combustion of paper, wood, and plastic as well as with NaCl particles. The collection of submicron particles was examined under conditions representing two typical indoor air flow rates for the HVAC filter and two cabin fan control levels for the ACA filter. For the HVAC filter, almost all the collection efficiency values exceeded 80%; for the ACA filter, the collect efficiencies were much lower (< 40%) for all the tested aerosols and flow rates. Both filters demonstrated lower collection efficiency for combustion aerosols as compared to NaCl. This finding was consistent for all tested particle sizes and flow rates. The difference was always statistically significant in terms of the total efficiency (combining all sizes); however, the size-specific analysis of the differences revealed that the significance level varied with the particle size and flow rate. When tested under their operational flow conditions, the HVAC filter showed significantly better performance than the ACA filter. It was concluded that the filter performance characteristics of the HVAC and ACA filters obtained using well-established salt aerosol challenges may not accurately predict the performance of these filters against combustion aerosol particles. The difference was attributed to the interactions between the particles and filter fibers.

Keywords

HVAC filter Automotive cabin air filter Combustion aerosols NaCl Collection efficiency


Related Article

Ozone Catalytic Oxidation of Gaseous Toluene over MnO2-Based Ozone Decomposition Catalysts Immobilized on a Nonwoven Fabric

Kazuhiko Sekiguchi , Yuki Kurita, Kenshi Sankoda, Norikazu Namiki, Fumio Yasui, Hajime Tamura
Accepted Manuscripts
DOI: 10.4209/aaqr.2017.01.0045
PDF

Novel Method for Preparing Controllable Nanoporous α-Fe2O3 and its Reactivity to SCR De-NOx

Haibo Liu, Zexin Zhang, Qian Li, Tianhu Chen , Changai Zhang, Dong Chen, Chengzhu Zhu, Yang Jiang
Volume: 17 | Issue: 7 | Pages: 1898-1908
DOI: 10.4209/aaqr.2017.05.0188
PDF

Effects of Nutrient Availability on the Biomass Production and CO2 Fixation in a Flat Plate Photobioreactor

Chih Ming Su, Hsin Ta Hsueh, Chi Ming Tseng, Dah Tong Ray, Yun Hwei Shen, Hsin Chu
Volume: 17 | Issue: 7 | Pages: 1887-1897
DOI: 10.4209/aaqr.2016.09.0386
PDF | Supplemental material

Removal of DPM from an Air Stream Using Micron-Scale Droplets

Lucas Rojas-Mendoza, Emily A. Sarver , John R. Saylor
Volume: 17 | Issue: 7 | Pages: 1865-1874
DOI: 10.4209/aaqr.2017.03.0093
PDF | Supplemental material
;