OPEN ACCESS

Articles online

Ventilation Control of Air Pollutant during Preventive Maintenance of a Metal Etcher in Semiconductor Industry

Category: Articles

Volume: 7 | Issue: 4 | Pages: 469-488
DOI: 10.4209/aaqr.2007.01.0007
PDF | RIS | BibTeX

Chih-Liang Chien1, Chuen-Jinn Tsai 1, Kwen-wen Ku1, Shou-Nan Li2

  • 1 Institute of Environmental Engineering, National Chiao Tung University, No. 75 Poai St., Hsinchu, Taiwan
  • 2 Energy and Environment Research Laboratories, Industrial Technology Research Institute (ITRI), Hsinchu, Taiwan

Abstract

Ventilation control efficiency of air pollutant emitted from a type P5000 metal etcher (Applied Materials, Inc.) during preventive maintenance was investigated in this study. Sulfur hexafluoride (SF6) gas of 1000 ppm was released at different flow rates at the bottom of the chamber to simulate the emission. When a large flow rate of 3130 L/min was vented from the venting port near the top of the chamber, the control efficiency of air pollutant is nearly 100%, whether the top of the chamber was open or enclosed with a specially-designed cover. The SF6 concentration at the breathing zone was found to be lower than the detection limit of the FTIR spectrometer. Numerical simulation of the flow and pollutant concentration fields yielded control efficiencies in good agreement with the experimental data. When the chamber was open, the control efficiency remained at 100% if the venting flow rate was greater than 1200 L/min; while the control efficiency decreased with decreasing flow rate. In comparison, the control efficiency with the specially-designed cover, which had a much smaller opening, was 100% for venting flow rates as low as 31.3 L/min.

Keywords

Cleanroom Pollutant dispersion Ventilation Indoor air pollution


Related Article

Quantitative Techniques for Measuring Cleanroom Wipers with Respect to Airborne Molecular Contamination

Angus Shiue, Shih-Cheng Hu , Chi-Hung Lin, Shin-In Lin
Volume: 11 | Issue: 4 | Pages: 460-465
DOI: 10.4209/aaqr.2011.03.0022
PDF

Effects of the Removal of 0.1 μm Particles in Industrial Cleanrooms with a Fan Dry Coil Unit (FDCU) Return System

Ti Lin, Yun-Chun Tung, Shih-Cheng Hu , Chen-Yen Lin
Volume: 10 | Issue: 6 | Pages: 571-580
DOI: 10.4209/aaqr.2010.03.0014
PDF

Critical Emissions from the Largest On-Road Transport Network in South Asia

Saroj Kumar Sahu , Gufran Beig, Neha Parkhi
Volume: 14 | Issue: 1 | Pages: 135-144
DOI: 10.4209/aaqr.2013.04.0137
PDF

Ambient Air Quality during Diwali Festival over Kolkata – A Mega-City in India

A. Chatterjee , C. Sarkar, A. Adak, U. Mukherjee, S.K. Ghosh, S. Raha
Volume: 13 | Issue: 3 | Pages: 1133-1144
DOI: 10.4209/aaqr.2012.03.0062
PDF
;